Posts

NSC Solution F1 Control Panel Cards are as below:

Loop Cards :

nsc loop card کارت لوپ

Loop card for “Solution F1” with 2 loops / 4 stub lines
■ 2 loops – each maximum 254 detectors / modules (Apollo: 2 x 126) –
or alternative 4 stub lines
■ cable length max. 3,500 m (2 x 2 x 0.8)
■ 8 user programmable open collector outputs
■ up to 127 loop sounders per loop can be activated at the same time
■ cable shielding monitored for open and short circuit
■ Earth fault detection

2. (Redundant Loop Cards)

nsc redundant loop card

Redundant Loop card for “Solution F1”
with 2 loops / 8 stub lines
■ As Loop card for “Solution F1” with 2 loops / 8 stub lines but
additionally with 100 % redundancy. This means the micro processor, the
RAM and the operating system memory are doubled on this card.
So there will be no failure in case of micro processor fault.

3. Conventional Cards

nsc conventional card کارت متعارف

Conventional detector card for 8 stub lines
■ compatible to almost all conventional detectors on the market
■ 32 detectors per line according German standards
■ 8 programmable open collector alarm outputs
■ Earth fault detection
■ Failure mode in case of micro-processor fault

4. (Redundant Conventional Cards)

nsc redundant conventional card

Conventional detector card with 100%
redundancy for 8 stub lines
■ as Conventional detector card for 8 stub lines but with 100 %.
That means the micro processor, the Ram and the operating system
memory are doubled on this card. So there will be no failure in case of
micro processor fault.

5. Relay Card

nsc relay card کارت رله ان اس سی

Relay card with 8 change over contacts
■ compatible to F1 fire detection system but usable as a universal
device in other systems too
■ 8 programmable change over contacts, each 250 V AC / 5 A

Download NSC Catalog